1000VA Protection Relay Testing K3063 , 10 Output Chann

1000VA Protection Relay Testing K3063 , 10 Output Channels

 

4 pairs Binary output
Capacity:250V/3A AC/DC
Power:1000VA

  

 Friendly PC software for easy operation!

 

K30 series relay tester is extremely design for overseas user, with Friendly PC software as your need, unique features and functions helps you all the way!

 

1. Unique self-protection system assure the powerful protection when instrument is operating, automatic stop the output when the network is abnormal ;
2. Unique power switch and amplifier technology, so the output precision and power efficiency and factor are increased, which conforms to international tendency of energy save and environmental protection;
3. With alarm function of housing grounding testing and external voltage input, to guaranty personal security;
4. Two in one of meter and source, with function of both internal and external testing, self-calibration, oscillograph, and the duration of each oscillograph reaches 50S (optional function);
5. Offer independent Aux. DC to tested devices, 0 ~ 300V/0.6A (Poleless and adjustable);
6. Function of transducer and energy meter testing (optional function);
7. Testing interface offer unique output monitoring function and Pre-curve-tracing function, helps more on the spot analysis;

 

Technical Data of K3063

 

Voltage generators

Setting 

Range

4-phase AC (L-N)

4 x 0 ... 130 V 

2-phase AC (L-L)

2 x 0 ... 260 V

Power

4-phase AC (L-N)

4 x 70VA,  at 0 ... 130 V

2-phase AC (L-L)

2 x 140VA,  at 0 ... 260 V

Accuracy

<0.07% reading + 0.03% range guaranteed 

at 0 ... 130 V

<0.02% reading + 0.01% range typical 

at 0-130V

Resolution

1mV

Current generators

Setting 

Range

6-phase AC (L-N)

6 x 0 ... 20 A

3-phase AC (2L-N)

3 x 0 ... 40 A (Group A II B)

1-phase AC (3L-N)

1 x 0 ... 120 A 

Power

6-phase AC (L-N)

6×250VA , at 0 ... 20A 

3-phase AC (2L-N)

3×450VA,  at 0 ... 40A (Group A II B) 

1-phase AC (3L-N)

1 x 1200 VA,  at 0 ... 120A (Max.)

Accuracy

<0.07% reading + 0.06% range guaranteed at 0-30A 

<0.02% reading + 0.02% range typical at 0-30A

Resolution

1mA

bigPhoto
 Mr. Vicky

Tel: 86-755-83418941
Contact to this supplier

Didn't find what you're looking for? Post Buying Lead or contact HiSupplier Customer Service Center  for help!

Related Search

Find more related products in following catalogs on Hisupplier.com

Company Info

Kingsine Electric Automation Co., Ltd, [China (Mainland)]


Business Type:Manufacturer
City: Shenzhen
Province/State: Guangdong
Country/Region: China (Mainland)

You May Like:

Product (5)